3C X 120 Sq.mm

Description

Description

Standards

  • Product
    BS 7846
  • Test
    BS 6387; IEC 60331-1 or 2; IEC 60332-3-24; IEC 60754; IEC 61034

These cables are widely used in Fire alarm systems ,emergency lightning power safety circuits when installed in conduits or protected trunking .

Conductor
Plain annealed high conductivity stranded bare copper class 2 to BS EN 60228

Fire barrier 
Mica Glass Tape

Insulation 
Cross Linked Polyethylene "XLPE"

Bedding
Halogen Free Flame retardant "HFFR" .

Armour
Galvanised steel wire armour "SWA".

Outersheath
Halogen Free Flame retardant "HFFR" .

Certficate of Product Approval

The product listed under this category are approved with LPCB ( LOSS PREVENTION CERTIFICATION BOARD) & QCDD (QATAR CIVIL DEFENSE DEPARTMENT) .

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Copper
Conductor flexibility
Class 2
Conductor shape
Sector-shaped
Insulation
XLPE
Core identification
Red,Blue,Yellow
Inner sheath
Halogen free flame retardant
Armour type
Galvanized steel wires
Outer sheath
Halogen free flame retardant
Colour
Black
Halogen free
Yes

Dimensional characteristics

Dimensional characteristics

Number of cores
3
Conductor cross-section
120 mm²
Approximate weight
5025 kg/km
Nominal outer diameter
40.9 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Max. DC resistance of the conductor at 20°C
0.153 Ohm/km
Permissible current rating in open air
353 A
Permissible current rating when buried
257 A
Thermal soil resistivity dry zone
2.5 °K.m/W

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Max. conductor temperature in service
90 °C
Short-circuit max. conductor temperature
250 °C
Bending factor when laying
12 (xD)
Ambient air temperature
30 °C
Ambient ground temperature
20 °C
Fire resistant
IEC 60331-1
Flame retardant
IEC 60332-3 Cat. C
Laying depth, center of system
700 mm
Max. pulling force during laying
50 N/mm2

Resources

Resources

Selling & delivery Information

Marking (by Embossing/Engraving)

FIRST Line:

ELECTRIC CABLE 600/1000 V BS 7846-F2 QICC-NEXANS ALSECURE PLUS NX400 No.of cores X Size  LPCB 1262b/01 YEAR

SECOND Line :

ELECTRIC CABLE 600/1000 V BS 7846-F2 QICC-NEXANS METER

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close